Our Specification

Standards Conformance

IEC 60439-1, BSEN 60439-1 AS 3439.1
IEC 60529, IEC 61641, IEC-61439 : 2009

Rates insulation voltage

Rates operation voltage

Rated impulse withstand voltage

Rated current

Ui 1000V AC

Ue 690V AC, 50Hz

Uimp 6kV

Ie 600A – 6000A

Rated short circuit withstand

* Main busbars

* Distribution busbars

Icw 80kA rms for 3 s

Ipk 176 kA

Icw 80kA 1s

Ipk 176kA

Arcing withstand-fault test

Ambient air temperature

Ingress protection provided by the enclosure

Forms of internal separation

Enclosure material

415V at 65 kA, pf=0.20

up to 50 degree celsius

IP20……IP43

1, 2a, 2b, 3a, 3b, 4a, 4b

Mild steel, electro-galvanized, stainless steel & galvanized iron

 

Standard colour finishing

 

Polyster powder paint ( wrinkle texture)

(Fair Grey) (interior & exterior)

thickness – 40 to 150 microns

 

 

Metal sheet thickness

 

 

1.2mm for distribution board

1.5mm for sub-switchboard

1.5 – 1.8mm for feeder pillars

1.8mm for doors / covers of floor-standing board

2.3mm for structural frame of floor-standing bd

Floor-Standing Board dimensions

* heights

* depths

* widths

 

1925, 2225, 2525 mm

650, 850, 1050, 1200 mm

400, 450, 500, 550, 600, 650, 750, 800, 850, etc

Busbar system
* Material
* Surface treatment
* Support material

 
Oxygen-free high conductivity
Tin-plated or PVC heat-shrinked sleeved
Fibreglass reinforced polyester